    Power contactor, AC-3 7 A, 3 kW / 400 V 1 NC, 230 V AC, 50 / 60 Hz 3-pole, Size S00 screw terminal

    <td class="TECellBase TE
    Product brand name SIRIUS
    Product designation Power contactor
    Product type designation 3RT2
    General technical data
    Size of contactor S00
    Product extension
    ● function module for communication No
    ● Auxiliary switch Yes
    Power loss [W] for rated value of the current
    ● at AC in hot operating state 1.2 W
    ● at AC in hot operating state per pole 0.4 W
    Power loss [W] for rated value of the current without load current share typical 4.2 W
    Surge voltage resistance
    ● of main circuit rated value 6 kV
    ● of auxiliary circuit rated value 6 kV
    maximum permissible voltage for safe isolation
    ● between coil and main contacts acc. to EN 60947-1 400 V
    Protection class IP
    ● on the front IP20
    ● of the terminal IP20
    Shock resistance at rectangular impulse
    ● at AC 6,7g / 5 ms, 4,2g / 10 ms
    Shock resistance with sine pulse
    ● at AC 10,5g / 5 ms, 6,6g / 10 ms
    Mechanical service life (switching cycles)
    ● of contactor typical 30 000 000
    ● of the contactor with added electronics-compatible auxiliary switch block typical 5 000 000
    ● of the contactor with added auxiliary switch block typical 10 000 000
    Reference code acc. to DIN 40719 extended according to IEC 204-2 acc. to IEC 750 K
    Reference code acc. to DIN EN 81346-2 Q
    Ambient conditions
    Installation altitude at height above sea level
    ● maximum 2 000 m
    Ambient temperature
    ● during operation -25 ... +60 °C
    ● during storage -55 ... +80 °C
    Main circuit
    Number of poles for main current circuit 3
    Number of NO contacts for main contacts 3
    Operating voltage
    ● at AC-3 rated value maximum 690 V
    Operating current
    ● at AC-1 at 400 V
    — at ambient temperature 40 °C rated value 18 A
    ● at AC-1
    — up to 690 V at ambient temperature 40 °C rated value 18 A
    — up to 690 V at ambient temperature 60 °C rated value 16 A
    ● at AC-2 at 400 V rated value 7 A
    ● at AC-3
    — at 400 V rated value 7 A
    — at 500 V rated value 6 A
    — at 690 V rated value 4.9 A
    ● at AC-4 at 400 V rated value 6.5 A
    ● at AC-5a up to 690 V rated value 15.8 A
    ● at AC-5b up to 400 V rated value 5.8 A
    ● at AC-6a
    — up to 230 V for current peak value n=20 rated value 4 A
    — up to 400 V for current peak value n=20 rated value 4 A
    — up to 500 V for current peak value n=20 rated value 3.8 A
    — up to 690 V for current peak value n=20 rated value 3.6 A
    ● at AC-6a
    — up to 230 V for current peak value n=30 rated value 2.7 A
    — up to 400 V for current peak value n=30 rated value 2.7 A
    — up to 500 V for current peak value n=30 rated value 2.5 A
    — up to 690 V for current peak value n=30 rated value 2.4 A
    Minimum cross-section in main circuit
    ● at maximum AC-1 rated value 2.5 mm²
    Operating current for approx. 200000 operating cycles at AC-4
    ● at 400 V rated value 2.6 A
    ● at 690 V rated value 1.8 A
    Operating current
    ● at 1 current path at DC-1
    — at 24 V rated value 15 A
    — at 110 V rated value 1.5 A
    — at 220 V rated value 0.6 A
    — at 440 V rated value 0.42 A
    — at 600 V rated value 0.42 A
    ● with 2 current paths in series at DC-1
    — at 24 V rated value 15 A
    — at 110 V rated value 8.4 A
    — at 220 V rated value 1.2 A
    — at 440 V rated value 0.6 A
    — at 600 V rated value 0.5 A
    ● with 3 current paths in series at DC-1
    — at 24 V rated value 15 A
    — at 110 V rated value 15 A
    — at 220 V rated value 15 A
    — at 440 V rated value 0.9 A
    — at 600 V rated value 0.7 A
    Operating current
    ● at 1 current path at DC-3 at DC-5
    — at 24 V rated value 15 A
    — at 110 V rated value 0.1 A
    ● with 2 current paths in series at DC-3 at DC-5
    — at 24 V rated value 15 A
    — at 110 V rated value 0.25 A
    ● with 3 current paths in series at DC-3 at DC-5
    — at 24 V rated value 15 A
    — at 110 V rated value 15 A
    — at 220 V rated value 1.2 A
    — at 440 V rated value 0.14 A
    — at 600 V rated value 0.14 A
    Operating power
    ● at AC-1
    — at 230 V rated value 6.3 kW
    — at 230 V at 60 °C rated value 6 kW
    — at 400 V rated value 11 kW
    — at 400 V at 60 °C rated value 10.5 kW
    — at 690 V rated value 19 kW
    — at 690 V at 60 °C rated value 18 kW
    ● at AC-2 at 400 V rated value 3 kW
    ● at AC-3
    — at 230 V rated value 1.5 kW
    — at 400 V rated value 3 kW
    — at 500 V rated value 3 kW
    — at 690 V rated value 4 kW
    Operating power for approx. 200000 operating cycles at AC-4
    ● at 400 V rated value 1.15 kW
    ● at 690 V rated value 1.15 kW
    No-load switching frequency
    ● at AC 10 000 1/h
    Operating frequency
    ● at AC-1 maximum 1 000 1/h
    ● at AC-2 maximum 750 1/h
    ● at AC-3 maximum 750 1/h
    ● at AC-4 maximum 250 1/h
    Control circuit/ Control
    Type of voltage of the control supply voltage AC
    Control supply voltage at AC
    ● at 50 Hz rated value 230 V
    ● at 60 Hz rated value 230 V
    Operating range factor control supply voltage rated value of magnet coil at AC
    ● at 50 Hz 0.8 ... 1.1
    ● at 60 Hz 0.85 ... 1.1
    Apparent pick-up power of magnet coil at AC
    ● at 50 Hz 27 V·A
    ● at 60 Hz 24.3 V·A
    Inductive power factor with closing power of the coil
    ● at 50 Hz 0.8
    ● at 60 Hz 0.75
    Apparent holding power of magnet coil at AC
    ● at 50 Hz 4.2 V·A
    ● at 60 Hz 3.3 V·A
    Inductive power factor with the holding power of the coil
    ● at 50 Hz 0.25
    ● at 60 Hz 0.25
    Closing delay
    ● at AC 9 ... 35 ms
    Opening delay
    ● at AC 3.5 ... 14 ms
    Arcing time 10 ... 15 ms
    Control version of the switch operating mechanism Standard A1 - A2
    Auxiliary circuit
    Number of NC contacts for auxiliary contacts
    ● instantaneous contact 1
    Operating current at AC-12 maximum 10 A
    Operating current at AC-15
    ● at 230 V rated value 10 A
    ● at 400 V rated value 3 A
    ● at 500 V rated value 2 A
    ● at 690 V rated value 1 A
    Operating current at DC-12
    ● at 24 V rated value 10 A
    ● at 48 V rated value 6 A
    ● at 60 V rated value 6 A
    ● at 110 V rated value 3 A
    ● at 125 V rated value 2 A
    ● at 220 V rated value 1 A
    ● at 600 V rated value 0.15 A
    Operating current at DC-13
    ● at 24 V rated value 10 A
    ● at 48 V rated value 2 A
    ● at 60 V rated value 2 A
    ● at 110 V rated value 1 A
    ● at 125 V rated value 0.9 A
    ● at 220 V rated value 0.3 A
    ● at 600 V rated value 0.1 A
    Contact reliability of auxiliary contacts 1 faulty switching per 100 million (17 V, 1 mA)
    UL/CSA ratings
    Full-load current (FLA) for three-phase AC motor
    ● at 480 V rated value 4.8 A
    ● at 600 V rated value 6.1 A
    Yielded mechanical performance [hp]
    ● for single-phase AC motor
    — at 110/120 V rated value 0.25 hp
    — at 230 V rated value 0.75 hp
    ● for three-phase AC motor
    — at 200/208 V rated value 1.5 hp
    — at 220/230 V rated value 2 hp
    — at 460/480 V rated value 3 hp
    — at 575/600 V rated value 5 hp
    Contact rating of auxiliary contacts according to UL A600 / Q600
    Short-circuit protection
    Design of the fuse link
    ● for short-circuit protection of the main circuit
    — with type of coordination 1 required gG: 35A (690V,100kA), aM: 20A (690V,100kA), BS88: 35A (415V,80kA)
    — with type of assignment 2 required gG: 20A (690V,100kA), aM: 16A (690V, 100kA), BS88: 20A (415V, 80kA)
    ● for short-circuit protection of the auxiliary switch required gG: 10 A (500 V, 1 kA)
    Installation/ mounting/ dimensions
    Mounting position +/-180° rotation possible on vertical mounting surface; can be tilted forward and backward by +/- 22.5° on vertical mounting surface
    Mounting type screw and snap-on mounting onto 35 mm standard mounting rail according to DIN EN 60715
    ● Side-by-side mounting Yes
    Height 58 mm
    Width 45 mm
    Depth 73 mm
    Required spacing
    ● with side-by-side mounting
    — forwards 10 mm
    — upwards 10 mm
    — downwards 10 mm
    — at the side 0 mm
    ● for grounded parts
    — forwards 10 mm

    Opinie